ABB AI880A 3BSE039293R1 Analog Input Module
ABB AI880A 3BSE039293R1 Analog Input Module
/ 2

ABB AI880A 3BSE039293R1 Analog Input Module

  • Manufacturer: ABB

  • Part Number: AI880A

  • Condition:New with Original Package

  • Product Type: Analog Input Module

  • Country of Origin: Sweden

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Features and Benefits

  • Channels: 8 channels for 0…20 mA, 4…20 mA, single-ended unipolar inputs
  • Configuration: Single or redundant configuration
  • Isolation: 1 group of 8 channels isolated from ground
  • Resolution: 12-bit
  • Loop Supervised DI Function
  • Alarm Limit: Configurable for field power outputs
  • Over/Under Range: Configurable for current inputs
  • Transmitter Supply: Current limited per channel
  • Diagnostics: Advanced on-board diagnostics
  • Certifications: SIL3 according to IEC 61508, Category 4 according to EN 954-1
  • Compliance: NAMUR recommendation NE43, supports configurable over- and under-range limits
  • HART Pass-through Communication (AI880A)

General Information

  • Article Number: 3BSE039293R1
  • Type: Analog Input
  • Signal Specification: 0…20 mA, 4…20 mA
  • Number of Channels: 8
  • Signal Type: Unipolar single-ended
  • HART: Yes
  • Redundancy: Yes
  • High Integrity: Yes
  • Intrinsic Safety: No
  • Mechanics: S800

Detailed Data

  • Input Impedance: 250 Ω with shunt stick TY801 (at current input)
  • Isolation: Groupwise isolated from ground
  • Under/Over Range: Over range: +12% (0…20 mA), +15% (4…20 mA)
  • Error: Max. 0.1%
  • Temperature Drift: Max. 50 ppm/°C
  • Input Filter (Rise Time 0-90%): 190 ms (HW filter)
  • Update Cycle Time: 10 ms
  • Current Limiting: Built-in current-limited transmitter power
  • Maximum Field Cable Length: 600 meters (656 yards)
  • Max Input Voltage (Non-destructive): 11 V d.c.
  • NMRR, 50Hz, 60Hz: > 40 dB
  • Rated Insulation Voltage: 50 V
  • Dielectric Test Voltage: 500 V a.c.
  • Power Dissipation: 2.4 W
  • Current Consumption +5 V Modulebus: 45 mA
  • Current Consumption +24 V Modulebus: Max 50 mA
  • Current Consumption +24 V External: 4 + transmitter current mA, max 260 mA

Diagnostics

  • Front LED’s: F(ault), R(un), W(arning)
  • Supervision: Internal voltage, Field power input, Field power output per channel
  • Status Indication of Supervision: Module error, Module Warning, Channel error

Environment and Certification

  • CE Mark: Yes
  • Electrical Safety: EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201
  • Hazardous Location: C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2
  • Marine Certification: ABS, BV, DNV, LR
  • Temperature, Operating: 0 to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C
  • Temperature, Storage: -40 to +70 °C (-40 to +158 °F)
  • Pollution Degree: Degree 2, IEC 60664-1
  • Corrosion Protection: ISA-S71.04: G3
  • Relative Humidity: 5 to 95%, non-condensing
  • Max Ambient Temperature: 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F)
  • Protection Class: IP20 according to IEC 60529
  • Mechanical Operating Conditions: IEC/EN 61131-2
  • EMC: EN 61000-6-4 and EN 61000-6-2
  • Overvoltage Categories: IEC/EN 60664-1, EN 50178
  • Equipment Class: Class I according to IEC 61140 (earth protected)
  • RoHS Compliance: DIRECTIVE/2011/65/EU (EN 50581:2012)
  • WEEE Compliance: DIRECTIVE/2012/19/EU