/ 2
ABB AI880A 3BSE039293R1 Analog Input Module
Manufacturer: ABB
-
Part Number: AI880A
Condition:New with Original Package
Product Type: Analog Input Module
-
Country of Origin: Sweden
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Features and Benefits
- Channels: 8 channels for 0…20 mA, 4…20 mA, single-ended unipolar inputs
- Configuration: Single or redundant configuration
- Isolation: 1 group of 8 channels isolated from ground
- Resolution: 12-bit
- Loop Supervised DI Function
- Alarm Limit: Configurable for field power outputs
- Over/Under Range: Configurable for current inputs
- Transmitter Supply: Current limited per channel
- Diagnostics: Advanced on-board diagnostics
- Certifications: SIL3 according to IEC 61508, Category 4 according to EN 954-1
- Compliance: NAMUR recommendation NE43, supports configurable over- and under-range limits
- HART Pass-through Communication (AI880A)
General Information
- Article Number: 3BSE039293R1
- Type: Analog Input
- Signal Specification: 0…20 mA, 4…20 mA
- Number of Channels: 8
- Signal Type: Unipolar single-ended
- HART: Yes
- Redundancy: Yes
- High Integrity: Yes
- Intrinsic Safety: No
- Mechanics: S800
Detailed Data
- Input Impedance: 250 Ω with shunt stick TY801 (at current input)
- Isolation: Groupwise isolated from ground
- Under/Over Range: Over range: +12% (0…20 mA), +15% (4…20 mA)
- Error: Max. 0.1%
- Temperature Drift: Max. 50 ppm/°C
- Input Filter (Rise Time 0-90%): 190 ms (HW filter)
- Update Cycle Time: 10 ms
- Current Limiting: Built-in current-limited transmitter power
- Maximum Field Cable Length: 600 meters (656 yards)
- Max Input Voltage (Non-destructive): 11 V d.c.
- NMRR, 50Hz, 60Hz: > 40 dB
- Rated Insulation Voltage: 50 V
- Dielectric Test Voltage: 500 V a.c.
- Power Dissipation: 2.4 W
- Current Consumption +5 V Modulebus: 45 mA
- Current Consumption +24 V Modulebus: Max 50 mA
- Current Consumption +24 V External: 4 + transmitter current mA, max 260 mA
Diagnostics
- Front LED’s: F(ault), R(un), W(arning)
- Supervision: Internal voltage, Field power input, Field power output per channel
- Status Indication of Supervision: Module error, Module Warning, Channel error
Environment and Certification
- CE Mark: Yes
- Electrical Safety: EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201
- Hazardous Location: C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2
- Marine Certification: ABS, BV, DNV, LR
- Temperature, Operating: 0 to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C
- Temperature, Storage: -40 to +70 °C (-40 to +158 °F)
- Pollution Degree: Degree 2, IEC 60664-1
- Corrosion Protection: ISA-S71.04: G3
- Relative Humidity: 5 to 95%, non-condensing
- Max Ambient Temperature: 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F)
- Protection Class: IP20 according to IEC 60529
- Mechanical Operating Conditions: IEC/EN 61131-2
- EMC: EN 61000-6-4 and EN 61000-6-2
- Overvoltage Categories: IEC/EN 60664-1, EN 50178
- Equipment Class: Class I according to IEC 61140 (earth protected)
- RoHS Compliance: DIRECTIVE/2011/65/EU (EN 50581:2012)
- WEEE Compliance: DIRECTIVE/2012/19/EU
You may also like