/ 2
CC-UPTA01 | Honeywell | Universal Pass Through Adapter
Manufacturer: Honeywell
-
Part Number: CC-UPTA01
Condition:New with Original Package
Product Type: Universal Pass Through Adapter
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Function
The CC-UPTA01 is a single-channel pass-through module that facilitates direct connectivity between Safety System or Safety field terminals (both live and return) and the field device. It operates without requiring external power.
Features
- Single Channel Pass Through Adapter: Provides seamless connectivity.
- 2 Wire AI/AO/DIL/DO/DOL: Supports various input and output configurations.
- System Powered Field I/O: Operates with system power.
- HART Pass Through: Supports HART protocol for communication.
- Interface Compatibility: Works with conventional Series C IOMs, Universal IO, and Universal Safety IO Module.
Parameter Specifications
- Dimensions: 118 mm (D) x 85.75 mm (W) x 10.0 mm (H)
- Assembly Option: Backplane mount, screwless
- Mistake Proof: Not Applicable
- Indicators: None
- Connections: 2 signal lines from Safety System to field side
Ambient Conditions
- Ambient Temperature (Operation): -40 °C to +70 °C
- Ambient Temperature (Storage/Transport): -40 °C to +85 °C
- Permissible Humidity (Operation): 5% to 95% (non-condensing)
-
Vibration:
- Non-Operational: 1g from 10 Hz to 150 Hz
- Operational: 0.5g from 10 Hz to 150 Hz
-
Shock:
- Operational: 5g
- Non-Operational: 15g
Enclosure and Mounting
- Assembly: Base plate and housing
- Mounting: Base plate with DIN rail mount and snap housing to the base plate
Electrical Specifications
- Power: 24V DC
- Max Current: 500mA
- Power Indication: Not Applicable
- Interface to Safety System: 37 pin DSUB (For SIC cable)
- Field Side Interface: Dedicated 3 terminals per channel
- Field Side Wire Gauge: 12-24 AWG
Compliance
- SIL Rating: SIL 3 as per IEC 61508
- Ingress Protection: IP20 as per IEC 60529
- Flammability Rating: V0 as per UL 94
- Conformance: ANSI/ISA 60079-0; 60079-15
- EMC Directive: IEC 61326-1 2012
- ATEX Certification: Ex ic IIC T4 Gc, Ex ec nC IIC T4 Gc
- IEC Ex Certification: Ex ic IIC T4 Gc, Ex ec nC IIC T4 Gc
- USA/Canada: Class I, Div. 2, Groups A, B, C, D T4; Class I, Zone 2, IIC T4
- Compliance: RoHS