Emerson | KJ3001X1-BG1 DO, 8-Channel, 24 VDC, Isolated Card
Emerson | KJ3001X1-BG1 DO, 8-Channel, 24 VDC, Isolated Card
/ 2

Emerson | KJ3001X1-BG1 DO, 8-Channel, 24 VDC, Isolated Card

  • Manufacturer: Emerson

  • Part Number: KJ3001X1-BG1

  • Condition:New with Original Package

  • Product Type: DO Isolated Card

  • Country of Origin: USA

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Overview

The Emerson KJ3001X1-BG1 is an 8-channel, isolated input/output card designed for reliable data acquisition in various industrial applications. It operates on 24 VDC, ensuring safe and efficient operation across a range of environmental conditions.

Power Specifications

  • Local Bus Power Rating: 12 VDC at 150 mA
  • Field Circuit Rating: 60 VDC at 1 A/channel

Environmental Specifications

  • Ambient Temperature: 0 to 60 °C
  • Shock: 10 g, ½ Sinewave for 11 ms
  • Vibration:
    • 1 mm Peak to Peak from 5 to 16 Hz
    • 0.5 g from 16 to 150 Hz
  • Airborne Contaminants: ISA-S71.04 – 1985, Class G3
  • Relative Humidity: 5 to 95% Non-Condensing
  • IP Rating: IP 20
  • Terminal Block Key Position: B5

Removal and Insertion

  • Field power must be removed before disconnecting the device.
  • The unit can be removed or inserted with system power energized only under specific conditions:
    • Compatible with KJ1501X1-BC1 System Dual DC/DC Power Supply with either 24 VDC or 12 VDC input power.
    • Primary circuit wiring inductance must be less than 23 µH.
    • Open circuit voltage (Ui) of 12.6 VDC and an Lo of less than 23 µH (including wire inductance) is required.
  • Non-sparking field circuits must be de-energized before device removal or insertion.
  • A terminal block fuse cannot be removed with field power energized for non-sparking circuits.
  • A rotary keying system ensures compatibility between I/O cards and terminal blocks after installation.

Maintenance and Adjustment

  • The unit contains no user-serviceable parts and should not be disassembled.
  • Calibration is not required.