Specifications

  • Input Type: Thermocouple and/or RTD
  • Voltage Rating: 24 VDC
  • Module Current Rating: 120mA
  • Input Channels:16 fully-isolated channels, channel-to-channel, channel-to-IOL, and channel-to-power supply common in 16 channel increments
  • Input Scan Rate: 1 second fixed by IOM (up to 16 channels/sec max.)
  • Channel Bandwidth: 0 to 4.7 Hz (-3 dB)
  • Nominal Input Range (TC only): -20 to +100 millivolts
  • Maximum Normal Mode Continuous Input Non-Damaging:
    • -10 to +10 volts (TC)
    • -1 to +2 volts @ 100 milliamps (RTD)
  • Gain Error (-20 to +100 millivolt range): 0.050% full scale max
  • Temperature Stability:
    • TC, millivolt inputs: +/-20 ppm per °C max
    • RTD inputs: +/-20 ppm per °C max
  • Long Term Drift: 500 ppm
  • Input Impedance: 1 megohm at DC (TC only)
  • Common Mode Voltage (CMV) with Respect to Power System Common, DC to 60 Hz:
    • Channel to Shield: +/-250 VDC or VAC RMS
    • Channel to Channel: +/-33 VDC or VAC RMS
  • Common Mode Rejection Ratio (CMRR), 50 or 60 Hz (with 1000 ohms source impedance max): 120 dB min
  • Voltage, Channel-to-Channel, DC to 60 Hz: +/-33 VDC or VAC RMS
  • Voltage, Channel-to-Shield, DC to 60 Hz: +/-250 VDC or VAC RMS
  • Crosstalk, DC to 60 Hz: 80 dB (120 dB at 50 and 60 Hz)
  • Normal Mode Rejection Ratio (NMRR) at 50/60 Hz: 60 dB min
  • Line Frequency Integration: Fixed selection of 50 Hz or 60 Hz
  • RTD Sensor Excitation Current: 1 milliamp
  • Cold Junction Compensation Range: -20 to +60 °C (± 0.5 °C typical)
  • TC Linearization Accuracy: ± 0.05 Ω / °C
  • Open Thermocouple Detection: Each conversion qualified, ≤ 1000 Ω = guaranteed no-trip; ≥ 1500 Ω guaranteed trip.
  • RTD Max Lead Resistance: 15 Ω
  • Surge Protection (Sensor Terminals): EN 61000-4-5 (for industrial locations, 1kV line to line, 2kV line to ground)
  • Surge Protection (Power/Serial Link with Cable Adapter Option): EN 61000-4-5 (for industrial locations, 1kV line to line, 2kV line to ground)