/ 2
MTL MTL5514 Switch / Proximity Detector Interface
Manufacturer: MTL
-
Part Number: MTL5514
Condition:New with Original Package
Product Type: Detector Interface
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Specifications
- Number of channels: One
- Location of switch: Zone 0, IIC, T6 hazardous area
- Location of proximity detector: Zone 0, IIC, T4–6 hazardous area, if suitably certified
- Hazardous-area inputs: Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR). Voltage applied to the sensor is 7 to 9V DC from 1kΩ ±10%.
-
Input/output characteristics:
- Outputs closed if input > 2.1mA (< 2kΩ in input circuit).
- Outputs open if input < 1.2mA (> 10kΩ in input circuit).
- Hysteresis: 200µA (650Ω) nominal.
- Line fault detection (LFD): User-selectable via switches on the side of the unit. Line faults are indicated by an LED. The line fault relay is energized and the channel output relay de-energized if an input line fault is detected.
- Safe-area output: Single pole relay with changeover contacts.
-
Relay characteristics:
- Response time: 10ms maximum.
- Contact rating (Safe Area): 250V AC, 2A, cosØ >0.7, 40V DC, 2A, resistive load.
-
LED indicators:
- Green for power indication.
- Yellow for channel status (on when output energized).
- Red for LFD indication (on when line fault detected).
- Maximum current consumption: 25mA at 24V DC.
- Power dissipation within unit: 0.6W at 24V.
- Operating temperature range: -20°C to +65°C (-6 to +149°F)
You may also like